Tuesday, October 07, 2008

Weil-McLain Recalls Ultra Series Boilers for Carbon Monoxide Hazard

Released: Tuesday, October 31, 2006 by CPSC

Oct

31

2006
In cooperation with the U.S. Consumer Product Safety Commission (CPSC), Weil-McLain, of Michigan City, Ind., is voluntarily recalling about 16,000 Weil-McLain Ultra Series Gas Boilers. These boilers were manufactured for use with natural gas, but could have a blue tag incorrectly indicating to installers that they are intended for use with LP (propane) gas. If an installer connects one of the boilers to LP gas without installing a propane conversion kit, carbon monoxide (CO) can build up due to incomplete combustion, posing a risk of CO poisoning.

Images

Recall Details

Product

Weil-McLain Ultra Series Gas Boilers

Description

The recall involves Weil-McLain Ultra 80, Ultra 105, Ultra 155, Ultra 230 and Ultra 310 condensing, high-efficient, gas-fired boilers for space heating. The user's manual and installation manual have "Ultra Gas-Fired Water Boiler" on the cover. The boilers are wrapped in a glossy silver/flat black jacket and either stand on the floor or are wall-mounted. The serial numbers range from CP5071716 through CP5327000. When the panel on the front of the boiler is removed, a bar-coded label with the serial number is located on the lower right hand side of the boiler itself. "Weil-McLain" is written on the front panel of the boilers.

Hazards

These boilers were manufactured for use with natural gas, but could have a blue tag incorrectly indicating to installers that they are intended for use with LP (propane) gas. If an installer connects one of the boilers to LP gas without installing a propane conversion kit, carbon monoxide (CO) can build up due to incomplete combustion, posing a risk of CO poisoning.

Incidents

Weil-McLain is aware of one incident where two consumers reported CO poisoning when the boiler installed in their home was connected to LP gas.

Remedy

Consumers who had a Weil-McLain Ultra series boiler installed for use with propane and have not already been contacted by their installer should contact the installer or a heating professional for a free safety inspection. If the boiler was not installed with a propane conversion kit, one will be installed at the time of the inspection at no charge. Heating professionals may contact Weil McLain Technical Service at (219) 879-6561 for more information.


  • Alternate Products

  • Suggest a safe alternate to this recalled product. Help others replace their recalled product with a similar item.



  • Articles

  • Have you found a related news article on this recall? Share the articles with the other viewers!



  • Comments

  • Voice your opinion on this recall. Do you have questions, concerns, or suggestions for the other viewers? Please feel free to sound off!